|
Basic Rainscreen Principles
At present most designers relate Rain Screen wall assembles to masonry
veneer and or masonry cavity wall. These assemblies have been
shown to work and over the years have been perfected to the point
where no testing and or performance warranties are required,
asked for or issued by the proponents of these systems namely
the masonry industry. The main feature of a brick veneer wall
assembly is the airspace (cavity) between the masonry and the
back up system, weep holes, vent holes and flashing. A brick
veneer is not air or water-tight and to this effect water most
likely will penetrate or saturate a brick veneer wall many times
over a period of one year. No damage is caused because the water
will exit through the weep holes or by evaporation caused by
air circulating in the cavity and the exterior exposure to the
sun and wind. The traditional nominal cavity width is 25mm, although
because of construction tolerances it can vary substantially.
This cavity is further partially blocked by mortar droppings
and masonry ties. It has been shown by experience that this reduction
and bridging does not affect the performance of the system if
additional safeguards are incorporated. These safer guidelines
are vent holes, weep holes and flashing. In addition, the system
is provided with protection from water penetration in the form
of moisture barrier if no insulation is placed in the cavity
or an air-vapour barrier on the warm side of the insulation if
insulation is placed in the cavity. At this time there are no
specific guidelines in codes and standards as to what is the
minimum or maximum cavity to achieve the drainage and venting
effectively.
The experience with the masonry veneer indicates that a cavity of
10 to 14mm with a contact area of less than 50% (blocked by approximately
50%) with weep holes spaced at 800mm having and area of 70mm2
vent holes at wall tops of similar spacing and area ensure that
any water entering the system will be directed out or will dry
by air circulation. The National Research Council of Canada recommends
a minimum of 9mm cavity if the assembly is to qualify as a vented
rain screen wall. The following section describes a panel which
when incorporated in the wall assembly will make the assembly
a vented rain screen.
|